| PRODUCT DESIGN | |
|---|---|
| APPLICABLE STANDARD | IS 694:2010 |
| CONDUCTOR | The conductors are drawn from 99.97% bright electrolytic grade copper with more than 100% conductivity. Annealed and bunched together. |
| TYPE INSULATION (HRFR PVC COMPOUND) | The bunched conductors are insulated with specially formulated heat-resistant flame-retardant PVC compound. The insulation process is carried out on modern high-speed extruders ensuring accuracy and consistency in performance. |
| FRLS COMPOUND | The bunched conductors are insulated with a special low smoke compound. During a fire, the FR-L insulation resists flame and minimizes smoke emission. |
| ZHFR COMPOUND | The bunched conductors are insulated with a specially formulated grade of halogen-free flame-retardant (HFFR) compound. The insulation does not melt or drip in case of fire. The emitted smoke is transparent, non-toxic, and minimal. |
| OPERATING TEMPERATURE RANGE | -15°C to Max. +70°C / +85°C |
| COLOUR | Red, Yellow, Blue, Black, Green, Gray (Other colors on request) |
| PACKING | Coils of 90m, 100m, 180m, 270m; Boxes and Reels |
| MARKING | The cables are printed with generic marking "NEONEX HRFR" |
| APPLICATION | This is a premium product of electrical wires from "NEONEX ". Ideal for wiring in residential and commercial complexes, high-rise buildings, hotels, hospitals, schools, colleges, etc., where population density is high. During a fire, these cables emit less smoke and toxic hydrochloric acid gas while retarding the spread of fire—enabling safe evacuation. |
| FEATURES |
|
| ISO CERTIFICATION | ISO 9001:2015, ISO 45001:2018, ISO 14001:2015, CE, RoHS |
| PRODUCT CERTIFICATION | IS 694:2010, 7098 P-1, TUV Rheinland Certificate No. R 60160877 |
| TECHNICAL DATA | |||||
|---|---|---|---|---|---|
| NOMINAL CROSS SECTIONAL AREA (mm²) | NUMBER / NOMINAL DIA OF WIRES (NOM.) | NOMINAL THICKNESS OF INSULATION (mm) | APPROX OVERALL DIA (±0.2 mm) | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C (Ω/km) | MAX. CURRENT CARRYING CAPACITY (AMPS) CASING / CONCEALED |
| 0.5 | 16/0.2 ** | 0.6 | 2.10 | 39.00 | 4 / 4 |
| 0.75 | 24/0.2 ** | 0.6 | 2.30 | 26.00 | 7 / 6 |
| 1 | 14/0.3 * | 0.6 | 2.70 | 18.10 | 12 / 11 |
| 1.5 | 22/0.3 * | 0.7 | 3.00 | 12.10 | 16 / 13 |
| 2.5 | 36/0.3 * | 0.8 | 3.50 | 7.41 | 22 / 18 |
| 4 | 56/0.3 ** | 0.8 | 4.10 | 4.95 | 29 / 24 |
| 6 | 84/0.3 ** | 0.8 | 5.10 | 3.30 | 37 / 31 |
| TEST DETAILS | ||||||||
|---|---|---|---|---|---|---|---|---|
| FR | FRLS | ZHFR | ||||||
| TEST | SPECIFICATION | SPECIFIED VALUE | TEST | SPECIFICATION | SPECIFIED VALUE | TEST | SPECIFICATION | SPECIFIED VALUE |
| CRITICAL OXYGEN INDEX | ASTM-D 2863 | 29 % MINIMUM | CRITICAL OXYGEN INDEX | ASTM-D 2863 | 29 % MINIMUM | CRITICAL OXYGEN INDEX | ASTM - D 2863 | 29 % MINIMUM |
| TEMPERATURE INDEX | ASTM - D 2863 | 250 °C MINIMUM | TEMPERATURE INDEX | ASTM - D 2863 | 250 °C MINIMUM | TEMPERATURE INDEX | ASTM - D 2863 | 250 °C MINIMUM |
| ACID GAS GENERATION | IEC 60754-1 | 20 % MAXIMUM | ACID GAS GENERATION | IEC 60754-1 | < 0.5% | |||
| SMOKE DENSITY RATING | ASTM - D 2843 | 60 % MAXIMUM | SMOKE DENSITY RATING | ASTM - D 2843 | 60 % MAXIMUM | |||