Trusted partner for high-quality wires & cables. Contact Us Today

Follow us on :

2 Core Aluminium / Copper

Technical Data (UN-ARMOURED CABLES) :- CABLE CODE : A2XY / 2XY

SIZE

NOMINAL INSULATION THICKNESS

MINIMUM INNER SHEATH THICKNESS

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIA OF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20 ° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XY

2XY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

mm2

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

2C X 4

0.70

0.30

1.80

12.00

180

240

7.410

4.61

36

32

45

40

2C X 6

0.70

0.30

1.80

13.00

220

300

4.610

3.08

45

42

57

52

2C X 10

0.70

0.30

1 .80

15 .00

280

400

3.080

1 .83

60

56

75

69

2C X 16

0.70

0.30

1.80

14.00

290

430

1.910

1.15

80

72

96

87

2C X 25

0.90

0.30

2.00

17.00

380

680

1.200

0.727

96

100

125

130

2C X 35

0.90

0.30

2.00

18.50

430

850

0.868

0.524

118

120

150

160

2C X 50

1.00

0.30

2.00

21.00

600

1150

0.641

0.387

145

146

175

195

2C X 70

1.10

0.30

2.00

23.00

750

1520

0.443

0.268

174

180

215

240

2C X 95

1.10

0.40

2.20

26.00

960

2050

0.320

0.193

210

230

260

300

2C X 120

1.20

0.40

2.20

28.00

1160

2450

0.253

0.153

235

260

290

335

2C X 150

1.40

0.40

2.20

31.00

1380

3050

0.206

0.124

265

305

325

385

2C X 185

1 .60

0.50

2.40

34.50

1720

3750

0.164

0.0991

300

345

365

445

2C X 240

1.70

0.50

2.60

39.00

2160

4900

0.125

0.0754

340

410

416

518

2C X 300

1.80

0.60

2.80

43.00

2660

6100

0.100

0.0601

385

475

470

600

2C X 400

2.00

0.60

3.00

48.00

3300

7850

0.0778

0.0470

450

550

530

680

Technical Data (ARMOURED CABLES) :- CABLE CODE : A2XFY/ 2XFY                                        

SIZE

NOMINAL INSULATION THICKNESS

MINIMUM INNER SHEATH THICKNESS

NOMINAL ARMOUR STRIP

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIA OF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XFY

2XFY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

mm2

mm

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

2C X 25

0.90

0.30

4X 0.80

1.40

18.00

610

915

1.200

0.727

96

100

125

130

2C X 35

0.90

0.30

4X0.80

1.40

19.50

700

1050

0.868

0.524

118

120

150

160

2C X 50

1.00

0.30

4X 0.80

1.40

21.50

830

1440

0.641

0.387

145

146

175

195

2C X 70

1.10

0.30

4X 0.80

1.56

24.50

1060

1910

0.443

0.268

174

180

215

240

2C X 95

1.10

0.40

4X0.80

1.56

27.00

1310

2480

0.320

0.193

210

230

260

300

2C X 120

1.20

0.40

4X 0.80

1.56

29.50

1510

2950

0.253

0.153

235

260

290

335

2C X 150

1.40

0.40

4X0.80

1.72

32.00

1760

3610

0.206

0.124

265

305

325

385

2C X 185

1 .60

0.50

4X 0.80

1.72

35.00

2210

4400

0.164

0.0991

300

345

365

445

2C X 240

1.70

0.50

4X 0.80

1.88

39.50

2610

5500

0.125

0.0754

340

410

416

518

2C X 300

1.80

0.60

4X0.80

2.04

43.00

3150

6700

0.100

0.0601

385

475

470

600

2C X 400

2.00

0.60

4X 0.80

2.36

49.00

4000

8600

0.0778

0.0470

450

550

530

680

Technical Data (ARMOURED CABLES) :- CABLE CODE A2XWY/ 2XwY        

SIZE

NOMINAL INSULATION THICKNESS

MINIMUM INNER SHEATH THICKNESS

NOMINAL ARMOUR WIRE

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIAOF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XWY

2XWY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

m m2

mm

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

2C X 4

0.70

0.30

1.40

1.24

14.00

400

480

7.410

4.610

36

32

45

40

2C X 6

0.70

0.30

1.40

1.24

15 .00

470

560

4.610

3.080

45

42

57

52

2C X 10

0.70

0.30

1.40

1.24

16.00

570

710

3.080

1.830

60

56

75

69

2C X 16

0.70

0.30

1.40

1.40

16.00

590

780

1.910

1.150

80

72

96

87

NOTE:

THE ABOVE DATA IS APPROXIMATE & SUBJECT TO MANUFACTURING TOLERANCE, 2. DELIVERY LENGTH TOLERANCE +/- 5%.

×

Hello!

Click one of our representatives below to chat on WhatsApp or send us an email to electrocabind@gmail.com

whatsapp ×