Technical Data (UN-ARMOURED CABLES) :- CABLE CODE : A2XY / 2XY                

SIZE

NOMINAL INSULATION THICKNESS

MINIMUM INNER SHEATH THICKNESS

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIAOF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX . CONDUCTOR DC RESISTANCE at 20 ° ; C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XY

2XY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

mm 2

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

4C X 4

0.70

0.30

1.80

14.00

230

350

7.410

4.61

35

31

44

39

4C X 6

0.70

0.30

1.80

15.00

290

440

4.610

3.08

44

41

55

50

4C X 10

0.70

0.30

1.80

17.00

370

640

3.080

1.83

58

53

74

68

4C X 16

0.70

0.30

1.80

19.00

460

800

1.910

1.15

75

70

95

86

4C X 25

0.90

0.30

2.00

23.00

600

1200

1.200

0.727

96

93

121

119

4C X 35

0.90

0.30

2.00

25.50

750

1600

0.868

0.524

116

116

146

147

4C X 50

1.00

0.30

2.00

29.50

980

2150

0.641

0.387

140

140

171

178

4C X 70

1.10

0.40

2.20

33.50

1300

2900

0.443

0.268

171

175

211

225

4C X 95

1.10

0.40

2.20

37.50

1700

3900

0.320

0.193

201

217

251

278

4C X 120

1 .20

0 .50

2.40

41.50

2150

4850

0.253

0.153

226

250

286

318

4C X 150

1.40

0.50

2.60

46.00

2600

6000

0.206

0.124

256

285

316

364

4C X 185

1.60

0.50

2.80

50.00

3200

7450

0.164

0.0991

286

330

356

421

4C X 240

1.70

0.60

3.00

56.00

4000

9650

0.125

0.0754

327

393

411

500

4C X 300

1.80

0.70

3.20

62.00

5000

12050

0.100

0.0601

371

452

461

572

Technical Data (ARMOURED CABLES) :- CABLE CODE : A2XFY/ 2XFY

SIZE

NOMINAL INSULATION THICKNESS

MINIMUM INNER SHEATH THICKNESS

NOMINAL ARMOUR STRIP

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIAOF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XFY

2XFY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

mm2

mm

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

4C X 10

0.70

0.30

4X 0.80

1.40

18.50

550

780

3.080

1.830

58

53

74

68

4C X 16

0 .70

0.30

4X 0.80

1.40

20.00

720

1050

1.910

1.150

75

70

95

86

4C X 25

0.90

0.30

4X 0.80

1.40

23.50

950

1550

1.200

0.727

96

93

121

119

4C X 35

0.90

0.30

4X 0.80

1.40

25.50

1050

1950

0.868

0.524

116

116

146

147

4C X 50

1.00

0.30

4X 0.80

1.56

29.50

1350

2550

0.641

0.387

140

140

171

178

4C X 70

1.10

0.40

4X 0.80

1.56

33.50

1700

3350

0.443

0.268

171

175

211

225

4C X 95

1.10

0.40

4X 0.80

1.56

37.50

2100

4450

0.320

0.193

201

217

251

278

4C X 120

1 . 20

0.50

4X 0.80

1.72

41.50

2600

5500

0.253

0.153

226

250

286

318

4C X 150

1 . 40

0.50

4X 0.80

1.88

46.00

3000

6700

0.206

0.124

256

285

316

364

4C X 185

1 . 60

0 . 50

4X 0.80

2.04

51.00

3700

8200

0.164

0.0991

286

330

356

421

4C X 240

1 .70

0.60

4X 0.80

2.20

57.00

4700

10300

0.125

0.0754

327

393

411

500

4C X 300

1.80

0.70

4X 0.80

2.36

63.00

5660

12800

0.100

0.0601

371

452

461

572

Technical Data (ARMOURED CABLES) :- CABLE CODE A2XWY/ 2XwY

SIZE

NOMINAL INSULATION THICKNESS

MINIMUM INNER SHEATH THICKNESS

NOMINAL ARMOUR WIRE

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIA OF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XWY

2XWY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

mm2

mm

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

4C X 4

0.70

0.30

1.40

1.24

15.50

510

590

7.410

4.61

35

31

44

39

4C X 6

0.70

0.30

1.40

1.24

16.50

590

730

4.610

3.08

44

41

55

50