Technical Data (UN-ARMOURED CABLES) :- CABLE CODE : A2XY / 2XY               

SIZE

NOMINAL INSULATION THICKNESS

NOMINAL OUTER SHEATH THICKNESS

APPROX. OVERALL DIA OF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING

ALUMINIUM CONDUCTOR

COPPER CONDUCTOR

A2XY

2XY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

mm 2

mm

mm

mm

Kg/Km

0hm/Km

AMPS

1C X 4

0.70

1.80

7.50

70

90

7.410

4.610

40

35

49

46

1C X 6

0.70

1.80

8.00

80

115

4.610

3.080

49

46

61

58

1C X 10

0.70

1.80

9.00

90

170

3.080

1.830

64

63

81

78

1C X 16

0.70

1.80

10.00

120

230

1.910

1.150

83

80

105

107

1C X 25

0.90

1.80

12.00

160

330

1.200

0.727

100

112

132

144

1C X 35

0.90

1.80

13.00

200

420

0.868

0.524

120

137

157

176

1C X 50

1.00

1.80

14.50

250

560

0.641

0.387

140

165

187

212

1C X 70

1.10

1.80

16.50

330

755

0.443

0.268

170

209

227

269

1C X 95

1.10

1.80

18.00

450

1020

0.320

0.193

205

256

267

331

1C X 120

1.20

1.80

20.50

510

1255

0.253

0.153

235

305

305

385

1C X 150

1.40

2.00

22.50

630

1555

0.206

0.124

270

345

340

435

1C X 185

1.60

2.00

24.50

800

1900

0.164

0.0991

300

390

385

500

1C X 240

1.70

2.00

27.00

950

2450

0.125

0.0754

350

455

440

595

1C X 300

1.80

2.00

30.00

1150

3050

0.100

0.0601

400

525

500

680

1C X 400

2.00

2.20

33.80

1500

3850

0.0778

0.0470

460

615

560

785

Technical Data (ARMOURED CABLES) :- CABLE CODE : A2XFaY / 2XFaY                                   

SIZE

NOMINAL INSULATION THICKNESS

NOMINAL ARMOUR ALUMINIUM STRIP

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIA OF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XFaY

2XFY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

m m2

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

1C X 95

1.40

4X 0.80

1.40

20.00

570

1160

0.320

0.193

205

256

267

331

1C X 120

1 . 50

4X0.80

1.40

22.00

670

1420

0.253

0.153

235

305

305

385

1C X 150

1 . 70

4X 0.80

1.40

24.00

770

1690

0.206

0.124

270

345

340

435

1C X 185

1 . 90

4X 0.80

1.40

26.00

920

2050

0.164

0.0991

300

390

385

500

1C X 240

2.00

4X 0.80

1.40

29.00

1150

2600

0.125

0.0754

350

455

440

595

1C X 300

2.10

4X 0.80

1.56

31.50

1355

3200

0.100

0.0601

400

525

500

680

1C X 400

2.40

4X0.80

1.56

35.50

1730

4200

0.0778

0.0470

460

615

560

785

Technical Data (ARMOURED CABLES) :- CABLE CODE : A2XWaY - 2XWaY                                

SIZE

NOMINAL INSULATION THICKNESS

NOMINAL DIA OF AL.ARMOUR WIRE

MINIMUM OUTER SHEATH THICKNESS

APPROX. OVERALL DIA OF CABLE ±2MM

APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C

NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR

A2XWaY

2XWaY

ALUMINIUM

COPPER

GROUND

AIR

GROUND

AIR

m m2

mm

mm

mm

mm

Kg/Km

Ohm/Km

AMPS

1C X 4

1.00

1.40

1.24

10.50

130

150

7.410

4.610

40

35

49

46

1C X 6

1.00

1.40

1.24

11.00

140

170

4.610

3.080

49

46

61

58

1C X 10

1.00

1.40

1.24

12.00

170

250

3.080

1.830

64

63

81

78

1C X 16

1.00

1.40

1.24

13.50

225

320

1.910

1.150

83

80

105

107

1C X 25

1.20

1.40

1.24

15.00

270

425

1.200

0.727

100

112

132

144

1C X 35

1.20

1.40

1.24

16.00

320

530

0.868

0.524

120

137

157

176

1C X 50

1.30

1.40

1.24

18.00

400

700

0.641

0.387

140

165

187

212

1C X 70

1.40

1.40

1.24

20.00

500

930

0.443

0.268

170

209

227

269

1C X 95

1.40

1.60

1.40

22.00

650

1250

0.320

0.193

205

256

267

331

1C X 120

1.50

1.60

1.40

24.00

750

1490

0.253

0.153

235

305

305

385

1C X 150

1.70

1.60

1.40

26.00

870

1790

0.206

0.124

270

345

340

435

1C X 185

1 .90

1 . 60

1.40

28.00

1050

2160

0.164

0.0991

300

390

385

500

1C X 240

2.00

1.60

1.40

31.50

1250

2700

0.125

0.0754

350

455

440

595

1C X 300

2 .10

1 . 60

1.56

34.50

1550

3350

0.100

0.0601

400

525

500

680

1C X 400

2.40

2.00

1.56

38.00

1950

4380

0.0778

0.0470

460

615

560

785

NOTE:

THE ABOVE DATA IS APPROXIMATE & SUBJECT TO MANUFACTURING TOLERANCE, 2. DELIVERY LENGTH TOLERANCE +/- 5%.

×